No. | ltem | Unit | Data | |||
1 | Rated voltage | KV | 40.5 | |||
2 | Rated insulation leve | 1min Power frequency withstand voltage (effective value) | 95 | |||
Lightning impulse withstand voltage (peak value) | 185 | |||||
3 | Rated frequency | Hz | 50 | |||
4 | Rated current | A | 630,1250,1600,2000,2500 | |||
5 | Rated short-time withstand curren | KA | 20 | 25 | 31.5 | |
6 | Rated peak withstand current | 50 | 63 | 80 | ||
7 | Rated short-circuit breaking current | 20 | 25 | 31.5 | ||
8 | Rated short-circuit making current (peak value) | 50 | 63 | 80 | ||
9 | Rated operating sequence | O-0.3s-CO-180s-CO | ||||
10 | Rated short circuit duration | S | 4 | |||
11 | Break time | Ms | ≤80 | |||
12 | Rated capacitor bank breaking current | A | 630/Back to back 400 | |||
13 | Rated short-circuit breaking current breaking times | Times | 20 | |||
14 | Mechanical life | 10000 | ||||
15 | Rated operating voltage | V | -110/~110,-220/~220 | |||
16 | Dimensions (WxHxD) | mm | 1246x1650x905 | |||
17 | weight kg | 466 |